
End-to-End Transformer Care
Touch the Hotspots Below to Explore End-to-End Transformer Care with SDMyers
Partial Discharge Inspections
Reliability-centered substation maintenance is built on gathering and analyzing as much condition data as possible before assets fail - enter partial discharge testing.
Partial discharge (PD) testing has delivered significant cost savings for SDMyers customers and protected their power transformers, switchgear, high voltage cable systems, and other electrical equipment from avoidable downtime.


How do PD inspections find failure modes so early?
PD inspections can help confirm transformer oil testing results or serve as a standalone detection technique for failure modes such as:
-
Insulation deterioration
-
Arcing/electrical discharges
-
Breakdown in transformer insulating liquid
Partial discharge inspections can pinpoint electrical issues in your network early, before they lead to catastrophic failure. Partial discharges emit energy in several ways: electrical pulse currents, dielectric losses, light, sound, increased gas pressure, and chemical reactions. Based on the energy emitted, multiple detection methods exist, such as Ultrasound and Transient Earth Voltage (TEV).
Ultrasound, the first line of defense, relies on changes in ultrasonic wave patterns. These can be detected long before other preventive maintenance tests detect other indicators.